Lugao's independently developed and produced Three Phase High Voltage 35KV 40.5KV Vacuum Circuit Breaker With Transformer is suitable for inter-city power distribution networks, ensuring safe operation of the power grid and providing short-circuit protection. It has good sealing performance and is easy to install and maintain. It has been praised by customers at home and abroad.
The Three Phase High Voltage 35KV 40.5KV Vacuum Circuit Breaker With Transformers are designed for use in three-phase power systems operating at 50 Hz and a rated voltage of 40.5 kV. They are used to disconnect and connect load current, overload current, and short-circuit current.

|
No. |
Description |
unit |
data |
||
| 1 |
Rated voltage |
KV | 40.5 | ||
| 2 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
KV | 95 |
|
Wet test |
80 | ||||
|
Lightning impulse withstand voltage (peak) |
185 | ||||
| 3 |
Rated current |
A |
1250;1600;2500 |
||
| 4 |
Rated short-circuit breaking current |
KA | 20;25;31.5 | ||
| 5 |
Rated operating sequence |
|
O-0.3s-CO- 180s-CO |
||
| 6 |
Rated short-circuit breaking current cycle |
bout |
12 | ||
| 7 |
Rated short-circuit closing current (peak value) |
KA | 50;63;80 | ||
| 8 |
Rated peak withstand current |
KA |
50;63;80 |
||
| 9 |
Rated short-circuit withstand current |
KA |
20;25;31.5 | ||
| 10 |
Rated short-circuit duration |
S | 4 | ||
| 11 |
Contact opening distance |
MM | 22±2 | ||
| 12 |
Contact opening distance |
MM | 4±1 | ||
| 13 |
Average trip speed |
M/S | 1.5±0.2 | ||
| 14 |
Average closing speed |
M/S | 0.7±0.2 | ||
| 15 |
Contact closure bounce time |
MS |
≤2 |
||
| 16 |
Three-phase main breaker (sub)switching synchronization time difference |
MS |
≤2 |
||
| 17 |
Closing time |
MS |
≤150 |
||
| 18 |
Trip time |
MS |
≤60 |
||
| 19 |
Mechanical lifespan |
bout |
10000 | ||
| 20 |
Rated operating voltage - Voltage of the auxiliary circuit |
V | DC110/220 AC110/220 | ||
| 21 |
DC resistance of each phase circuit (excluding the transformer) |
μΩ |
≤100 |
||
| 22 |
Weight |
KG | 800 | ||
• Ambient Air Temperature: Upper Limit +40°C, Lower Limit -30°C (General Areas), -40°C (Altitude in Cold Areas);
• Altitude: ≤ 1000m (As altitude increases, the rated insulation level increases accordingly);
• Evening Wind Pressure: No more than 700Pa (equivalent to a wind speed of 34m/s);
• Seismic Intensity: No more than 8°C;
• Pollution Degree: Level IV;
• Maximum Daily Temperature Difference: No more than 25°C