Lugao's independently developed and produced Three-Phase High Voltage 35KV 40.5KV Vacuum Circuit Breaker With Transformer is suitable for inter-city power distribution networks, ensuring safe operation of the power grid and providing short-circuit protection. It has good sealing performance and is easy to install and maintain. It has been praised by customers at home and abroad.
The ZW7-40.5 series outdoor high-voltage vacuum circuit breakers are designed for use in three-phase power systems operating at 50 Hz and a rated voltage of 40.5 kV. They are used to disconnect and connect load current, overload current, and short-circuit current.
No. |
Description |
unit |
data |
||
1 |
Rated voltage |
KV | 40.5 | ||
2 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
KV | 95 |
Wet test |
80 | ||||
Lightning impulse withstand voltage (peak) |
185 | ||||
3 |
Rated current |
A |
1250;1600;2500 |
||
4 |
Rated short-circuit breaking current |
KA | 20;25;31.5 | ||
5 |
Rated operating sequence |
|
O-0.3s-CO- 180s-CO |
||
6 |
Rated short-circuit breaking current cycle |
bout |
12 | ||
7 |
Rated short-circuit closing current (peak value) |
KA | 50;63;80 | ||
8 |
Rated peak withstand current |
KA |
50;63;80 |
||
9 |
Rated short-circuit withstand current |
KA |
20;25;31.5 | ||
10 |
Rated short-circuit duration |
S | 4 | ||
11 |
Contact opening distance |
MM | 22±2 | ||
12 |
Contact opening distance |
MM | 4±1 | ||
13 |
Average trip speed |
M/S | 1.5±0.2 | ||
14 |
Average closing speed |
M/S | 0.7±0.2 | ||
15 |
Contact closure bounce time |
MS |
≤2 |
||
16 |
Three-phase main breaker (sub)switching synchronization time difference |
MS |
≤2 |
||
17 |
Closing time |
MS |
≤150 |
||
18 |
Trip time |
MS |
≤60 |
||
19 |
Mechanical lifespan |
bout |
10000 | ||
20 |
Rated operating voltage - Voltage of the auxiliary circuit |
V | DC110/220 AC110/220 | ||
21 |
DC resistance of each phase circuit (excluding the transformer) |
μΩ |
≤100 |
||
22 |
Weight |
KG | 800 |
• Ambient Air Temperature: Upper Limit +40°C, Lower Limit -30°C (General Areas), -40°C (Altitude in Cold Areas);
• Altitude: ≤ 1000m (As altitude increases, the rated insulation level increases accordingly);
• Evening Wind Pressure: No more than 700Pa (equivalent to a wind speed of 34m/s);
• Seismic Intensity: No more than 8°C;
• Pollution Degree: Level IV;
• Maximum Daily Temperature Difference: No more than 25°C